All loads of a power plant can be modeled by a two-terminal network of
passive elements (resistors, inductors, capacitors, without any energy
sources) with a total complex impedance
![$\displaystyle Z=R+jX=\vert Z\vert e^{j\angle Z}=\vert Z\vert e^{j\phi},\;\;\;\;...
...\vert Z\vert=\sqrt{R^2+X^2}\\ \angle Z=\phi=\tan^{-1}(X/R)>0
\end{array}\right.$](img1056.svg) |
(391) |
As the loads are typically inductive (e.g., electric motors, transformers),
i.e.,
, the phase angle
of the impedance is
positive. We are concerned with the energy consumption (by
) and
storage (in
) in the load. Let the input voltage to the load network
be:
![$\displaystyle v(t)=\sqrt{2}V_{rms} \cos(\omega t),\;\;\;\;\dot{V}=\sqrt{2}V_{rms}\angle 0$](img1059.svg) |
(392) |
then the current through the power transmission line and load can be found:
![$\displaystyle \dot{I}=\frac{\dot{V}}{Z}=\frac{\sqrt{2}V_{rms}}{\vert Z\vert\ang...
...
=\sqrt{2}I_{rms}\angle(-\phi),\;\;\;\;i(t)=\sqrt{2}I_{rms} \cos(\omega t-\phi)$](img1060.svg) |
(393) |
where
is the RMS or effective value of the current.
Note that the current is lagging the voltage by an angle
.
Consider the instantaneous power of the load defined as the product
of the voltage and current:
where we have defined
![$\displaystyle p(t)=2\cos^2(\omega t)=1+\cos 2\omega t,\;\;\;\;\;\;
q(t)=2\cos(\omega t)\sin(\omega t)=\sin 2\omega t$](img1068.svg) |
(395) |
and
- Apparent Power (in volt-amperes):
- Real power (in Watts):
as the
- Reactive power (in volt-ampere reactive or
VAR):
The plots below show that the instantaneous power
can be
represented as either a product of
and
, or a weighted
sum of the real power
and reactive power
.
We note that
![$\displaystyle \frac{1}{T}\int_T p(t)dt=\frac{1}{T}\int_T [1+cos(2\omega t)] dt=1
\;\;\;\;\;\;
\frac{1}{T}\int_T q(t)dt=\frac{1}{T}\int_T \sin(2\omega t) dt=0$](img1075.svg) |
(396) |
Consider the average power over one period
:
We see that
- The real power
represents the average power dissipation
by the load over one period
;
- The reactive power
is not consumed but converted back
and forth between the energy source and the energy storing (inductive)
elements in the load.
The apparent power
can be considered as the magnitude of
a complex product of
and
:
![$\displaystyle \dot{V}\overline{\dot{I}}=V_{rms}\angle 0\; I_{rms}\angle \phi=V_{rms}I_{rms}\angle \phi
=S(\cos\phi+j\;\sin\phi)=P+jQ$](img1083.svg) |
(398) |
On the other hand, as
, the above can
also be written as:
![$\displaystyle \dot{V}\overline{\dot{I}}=Z\dot{I}\overline{\dot{I}}
=(R+jX)\dot{I}\overline{\dot{I}}=RI^2_{rms}+jX I^2_{rms}$](img1085.svg) |
(399) |
Comparing the two expressions of
above, we get:
![$\displaystyle \left\{ \begin{array}{l}
P=I^2_{rms}R=S\;\cos\phi \\
Q=I^2_{rms}X=S\;\sin\phi \\
S=I^2_{rms}Z \end{array} \right.$](img1087.svg) |
(400) |
the last equation is due to
![$\displaystyle S^2=P^2+Q^2=I^4_{rms}(R^2+X^2)=I^4_{rms}Z^2=(I^2_{rms}Z)^2$](img1088.svg) |
(401) |
We see that
- The apparent power is
;
- The real power is
, which is dissipated by the
resistive component
of the load;
- The reactive power is
, which is stored in and
released from the reactive component
of the load.
Improvement of Power Factor
The Power factor is defined as
![$\displaystyle \lambda\stackrel{\triangle}{=}\cos \phi < 1$](img1092.svg) |
(402) |
It is desirable to maximize the power factor
by reducing
,
for higher efficiency of the power transmission system, i.e., to deliver
the real power
to the load with minimum reactive power
(thereby
minimum current and power dissipation along the transmission line).
To do so, we can include a
shunt capacitor
to cancel the inductive effect in the system, thereby reducing
and increasing
.
The most straight forward way is to add the shunt capacitor
in series with the inductive load, so that the
inductive reactance
is completely canceled by the
capacitive reactance
.
However, we also note that at resonance, the voltages across
and
are
times the voltage across
, which is the same as the
source voltage (see this page):
![$\displaystyle \dot{V}_L=jQ\dot{V}_R,\;\;\;\;\;\dot{V}_C=-jQ\dot{V}_R$](img1098.svg) |
(403) |
the voltage across the inductive load
becomes
,
which could be much higher than the expected source voltage
(without capacitor
) if
is large. Consequently, improper
operation of the load or even damage may result.
The right way to compensate for the inductive impedance of the circuit
is to include the shunt capacitor
in parallel to the inductive load
so that it still gets the expected voltage.
Now the overall load becomes
We need to find the capacitance
so that the new phase angle
is zero, i.e., the phases of the numerator
and denominator need are the same:
Solving this equation for
we get:
![$\displaystyle C_p=\frac{L}{R^2+\omega^2 L^2}
=\frac{1}{R^2/L+\omega^2 L}<\frac{1}{\omega^2L}=C_s$](img1108.svg) |
(406) |
Now the voltage across the inductive load is still the same as the voltage
source as expected, and another benefit is that the required capacitance
is smaller than the capacitance
required for the series
approach.
Power factor correction
Shunt capacitors
To reduce the cost of a large capacitance needed for the phase angle of
the load to be reduced to zero
so that
, it
is acceptable for the improved power factor to be less than 1, e.g., 0.95.
In this case, the phase angle of the load is
![$\displaystyle \phi=\angle Z'=\tan^{-1}\left(\frac{\omega L}{R}\right)-\tan^{-1}\left(\frac{\omega RC}{1-\omega^2 LC}\right)=\cos^{-1}\; 0.95=18.2^\circ$](img1113.svg) |
(407) |
Solving this equation for
we get the required capacitance. As now we have
![$\displaystyle \tan^{-1}\left(\frac{\omega L}{R}\right)>\tan^{-1}\left(\frac{\omega RC}{1-\omega^2 LC}\right)$](img1114.svg) |
(408) |
i.e.,
![$\displaystyle \frac{\omega L}{R}>\frac{\omega RC}{1-\omega^2 LC}$](img1115.svg) |
(409) |
we get an even smaller capacitance which is more practically implementable:
![$\displaystyle C<\frac{L}{R^2+\omega^2 L^2}=\frac{1}{R^2/L+\omega^2L}$](img1116.svg) |
(410) |